JG Pears CHP: catching electrical discharge damage before it spreads
A combined heat and power station with electrical discharge (EDM) damaging motor bearings. Wireless monitoring now catches changes within hours.

Routine condition monitoring picked up abnormal electrical discharge on motor bearings around the site.
- A large equipment maker installed harmonic filters to improve power quality. This did not remove the stray frequencies on the motors.
- We pulled a fan bearing to inspect it and judge how fast damage was developing.
- Copper earthing was fitted to reduce discharge. It helped, but not enough.
Electrical discharge damage can progress very quickly, so occasional manual checks were not enough. We installed wireless condition monitoring on the affected machines. Signals are now monitored continuously and any degradation is seen straight away.
EDM can break down grease early, which then leads to rapid bearing damage. Anomaly detection flagged rising friction on a boiler feed pump motor. The site greased the bearing straight away and friction returned to normal.

Cost avoided is estimated from a previous similar failure on site: £10,000 repair plus two days offline at £250,000 per day.
“Uie's collaborative support has been invaluable to us. We can really trust in them to protect our plants from outside risks.”
JG Pears CHP
Seeing bearing failures you can't explain?
We will help you find out whether electrical discharge is the cause.